< Marsh Bellofram Group of Companies < Diversified Electronics < Power Alerts < GFD Series
GFD
Downloadable Files:
PDF icon GFD Series
GFD
  • For Use on Un-Grounded Systems
  • Detects & Indicates Phase of First Ground Fault
  • Horizontal and Vertical Mount Versions
  • Easy Installation in Conduit Knockout
Product Detail:
The ATC Diversified Electronics GFD Series is intended for the use on ungrounded systems to detect and indicate the phase of the first ground fault condition. This enables corrective action to avoid the potential hazards resulting from a second ground fault.

With nominal 3 phase line voltage applied, a flashing NORMAL green LED gives indication of a non-fault condition and integrity of the wire connection to the corresponding phase.

A flashing red LED gives positive FAULT indication of either a
phase-to-ground fault, or a lost connection to the corresponding phase.

NOTE: Distributed capacitance to ground or equally loaded phases
to ground will de-sensitize detection and will require lower
phase-to-ground resistance to produce a FAULT indication.
GFD Series 3-Phase Ground Fault Display
Part Numbers:
Model Number
Description
GFD-100
Vertical Mount
GFD-200
Horizontal Mount
Options:
Consult Factory
Cart:
Consult Factory
Purchase Details:
 
Product Contact:
Specifications:
Nominal Voltage 208-600 VAC, ±10%, Phase-to-Phase, 50/60 Hz
Max. Continuous Voltage 660 VAC, Phase-to-Phase
Wiring Error Protection Yes
Detection Threshold 11.7 k Ω ±20% @ 50 Hz; 9.3 k  Ω ±20% @ 60 Hz Single Phase-to-Ground
Detector Induced Fault Current 50 Hz 7.5 mA @ 600 VAC (1 Phase-to-Ground shorted)
60 Hz 9 mA @ 600 VAC (1 Phase-to-Ground shorted)
Fresnel Lens Indicators Normal (3) Green LEDs, 2 Flashes/Sec
Fault (3) Red LEDs, 2 Flashes/Sec
Apparent Power Required 50 Hz 2.5 VA @ 600 VAC
60 Hz 3 VA @ 600 VAC
Temperature Rating Operate 32° to 131°F (0° to 55°C)
Storage -49° to 185°F (-45° to 85°C)
Enclosure 94V-0 Flame Retardant Black ABS Plastic, Panel Mount w/1⁄4" Plastic Electrical Conduit Adapter, Encapsulated for Environmental Protection
Terminations (4) 2 ft., 18 AWG, 600V, 105°C PVC Stranded Wire w/ Wire Pin Terminations, Jacketed with 18" Slit Nylon Corrugated Tubing, .556" O.D.
Weight NET: 3.52 oz
Shipping: 5.12 oz